Jiangsu Guangyang Dynamic Environmental Equipment Co.,ltd

Tel:+0086-(0)510-87896688/87891880 

Fax:+0086-(0)510-87896699

Address:Industry  Area,East Town of  GaoCheng,YiXing City,JiangSu Province,China

Post code:214214

E-mail:sh@gysh.com.cn

Website:www.gysh.com.cn

Condensate Water Fine Treatment

Condensate water generally refers to the water cooled and condensed by the circulating cooling water from the steam produced in the boiler after the steam turbine has done work. In fact, the condensate water of the hot well of the condenser also includes

Collection share


Ⅰ.Generation of Condensate Water

  Condensate water generally refers to the water cooled and condensed by the circulating cooling water from the steam produced in the boiler after the steam turbine has done work. In fact, the condensate water of the hot well of the condenser also includes draining water produced in the high-pressure heater (Normal draining water that doesn’t enter the hot well), the low-pressure heater (Draining water refers to the water condensed by the feed water that is heated the heater) and so on. Due to the inevitable water vapor loss in the thermal system, a certain amount of supplemental water (Desalination tank water) should be replenished to the thermal system. So, condensate water mainly includes the condensate water from the steam produced in the boiler after the steam turbine has done work, all kinds of draining water and supplemental water of the boiler.


Ⅱ.Purpose of Fine Treatment

Condensate water can be contaminated to a certain extent for some reason, probably as follows:

1)The main cause of condensate water pollution is cooling water leaks from the defective part of the condenser to the condensate water. The defective part of the condenser is usually at the junction between the tube pipes and the tube plates inside the condenser. Because of the change of the working conditions for the equipment, mechanical stress will be produced inside the condenser. Even if the production and installation of the condenser is of good quality, seepage or leakage of the circulating cooling water may still occur when the condenser works. The cooling water contains more suspended substances, colloidal particles and salts, which will inevitably affect the quality of the condensate water.

2) Pollution of Metal Corrosion Products

The pipes and equipment of the condensate water system may be corroded for some reason, so metal corrosion products are often found in the condensate water. It mainly includes the iron oxides and copper oxides (The equipment in our company's thermal system basically don’t contain copper material). The forms of iron are mainly Fe2O3, Fe3O4, and they are in the suspended and colloidal state. In addition, there are also various iron ions. The content of corrosion products in the condensate water is related to the running condition of the equipment. There are more metal corrosion products in the condensate water at the start-up initial stage of the equipment, and the content of impurities may also increase when the load of the equipment is unstable.

3) Impurities Brought by the Supplemental Water of the Boiler

The outlet water of the chemical water treatment mixed bed is the supplemental water of the boiler, which generally enters into the thermal system from the condenser. Due to the strict control of the outlet water in the mixed bed in operation, the impurity content of the supplemental water is very small, and its water quality requirements are: DD ≤ 0. 2 μs/cm, SiO2 ≤ 20 μg/L. If the outlet water of the mixed bed is not qualified, it may cause pollution to the condensate water.

Due to the above reasons, the condensate water is more or less polluted, but the equipment with supercritical parameters has a high requirement for the quality of the feed water, so it is necessary to conduct further purification process to the condensate water, that is, to conduct fine treatment to the condensate water.


Ⅲ.Technology of the Treatment System

The condensate water fine treatment system adopts the middle-pressure condensate water mixed bed system,namely, the combination of front filter and high-speed mixed bed. It can also be regarded as a kind of internal or external regenerating system after the resins in the mixed bed lose efficacy. The external regenerating system mainly includes separation tower, anion-exchange tower and cation-exchange tower (“Three Towers"). In addition, it also includes acid and alkali equipment, hot water tank, washing pump, Roots fan, airs storage tank and so on.

1.Pre-filter

  This pre-filter is used to remove suspended substances, colloid matters, corrosion products and oils from the condensate water, which is mainly used to remove iron from the condensate water, clean off silicic acid and short the operation time of the system when the system is started. In addition, the removal of the substances with larger particle size can prolong the running cycle and service life of the resin. When the pressure difference between the inlet and outlet of the current pre-filter reaches the set value, the pre-filter needs to be backwashed. Water enters the pre-filter from the outlet at the bottom to backwash the filter materials, and the outlet water is discharged from the inlet (its flow direction is just opposite the flow direction of the operating water).Injecting air enter in the pre-filter to make the filter materials loose can enhance the backwashing effect.

2.High-speed Mixed Bed

It is mainly used to remove the salts in the water (All kinds of anions and cations) as well as impurities such as suspended substances and colloid matters that leak from pre-filter. There is the mixed resin of strong acid cation resin and strong alkali anion resin in the mixed bed. Cations in the condensate water are removed by reacting with the anion resin, and anions in the condensate water are removed by reacting with the anion resin. After both kinds of the resins lose efficacy, the anion resin can be regenerated by acid and the anion resin by alkali.

3.Regeneration Auxiliary Equipment

This equipment is mainly used in the regeneration process of resins and includes acid-alkali storage tank, acid-alkali injector, regeneration water pump, etc. 


Ⅳ.Operation and Control

 The control procedures of the condensate water fine treatment system include procedures of operation, shutdown and regeneration of the mixed bed, and the control range includes pre-filter, mixed bed and external regeneration unit; This system is designed to have the operation, backwash and shutdown of the pre-filter, the operation, shutdown and regeneration of the mixed bed and so on. After the completion of each part of the procedure is confirmed by workers, the next part of the procedure can be operated. In addition, the procedures can be set to the manual control mode. Each valve can also be operated by the solenoid valve in the solenoid valve box. The control system adopts computer to conduct the monitoring, with CRT display and keyboard.

The entrances of each pre-filter and mixed bed are equipped with flowmeter, boost bypass valve, and pressure transmitter. Flowmeter is used to monitor the condensate water flow passing through the pre-filter and the mixed bed, and it can output signals and accumulate the periodic water yield; The function of the boost bypass valve is to ensure the gradual increase of the inlet pressure before the pre-filter and the mixed bed are put into operation and to void the impact on pre-filter and the mixed bed caused by the sharp increase of the inlet pressure. The pressure changes are monitored by pressure transmitter.

The outlet of each mixed bed is equipped with conductivity meter, silicon meter and sodium meter to monitor the outlet water quality of the mixed bed. When a certain outlet water index is not up to standard, the backup mixed bed is put into operation, the invalid mixed bed is out of service and its regeneration procedure starts. pH meters on the sodium meter and the main pipe are the main monitoring devices for the NH+4/OH- type mixed bed operation.

The outlet main pipe of the mixed bed is equipped with conductivity meter, silicon meter and sodium meter to monitor the outlet water quality of the fine treatment system.

The main exhaust pipes of the pre-filter and the mixed bed are equipped with liquid level switch to automatically monitor whether the pre-filter and the mixed bed are filled with water.

The resin regeneration procedure is usually carried out manually according to the operation rules for regeneration operation.

Condensate Water Fine Treatment
Condensate water generally refers to the water cooled and condensed by the circulating cooling water from the steam produced in the boiler after the steam turbine has done work. In fact, the condensate water of the hot well of the condenser also includes
Long press to look detail
Long by picture save/share
INQUIRY

enquiry form:

  • Please enter the verification code

Inquiry Content:


You have no items to require

Add Successfully
图片展示

Jiangsu Guangyang Dynamic Environmental Equipment Co.,ltd

Tel:+0086-(0)510-87896688/87891880 

Fax:+0086-(0)510-87896699

Address:Industry  Area,East Town of  GaoCheng,YiXing City,JiangSu Province,China

Post code:214214